Title: Grid-connected inverter evaluation and experimental validation
Authors: Nur Aisyah Jalalludin
Goro Fujita
Conference Name: 8th SEATUC Symposium
Keywords: Electric power systems
Voltage
Conference Date: 2014-03-04
Conference Location: Universiti Teknologi Malaysia
Abstract: This paper investigates the effect of using a grid-connected inverter to the distribution system by experimental study. A power conditioner is used in this study and its operation is evaluated according to the electric distribution legislation. Several tests are conducted to validate the compatibility of the power conditioner in grid-connected mode. The output current and voltage are analyzed to confirm the normal operating condition while considering the frequency and harmonics limitations. Based on the results, the power conditioner stops operating when any disturbances such as frequency and voltage fluctuations are detected in the connection, and the values of the harmonics in the output current along with the power factor are verified to be in range in accordance to the conditions set by Japan Electrical Safety and Environment Technology Laboratories (JET).
Pages: 98
Call Number: LB2301.S433 2014 sem
Publisher: Universiti Teknologi Malaysia
URI: https://ptsldigital.ukm.my/jspui/handle/123456789/772970
Appears in Collections:Seminar Papers/ Proceedings / Kertas Kerja Seminar/ Prosiding

Files in This Item:
There are no files associated with this item.