Please use this identifier to cite or link to this item: https://ptsldigital.ukm.my/jspui/handle/123456789/579011
Title: Field evaluation of magnetic actuator driven switchgear in Malaysia
Authors: Mohd Dzaki (TNB)
Mohd Amir (TNB)
Sanuri Ishak (TNB)
Keywords: Magnetic actuator
Medium voltage switchgear
Condition monitoring
Life cycle
Issue Date: Feb-2017
Description: Magnetic actuator driven switchgear is a new medium voltage switchgear technology. In this switchgear, the conventional spring mechanism which is used to operate the circuit breaker is replaced with a magnetic actuator mechanism. The suitability of this technology in the Malaysian utility network specifically in highly loaded areas with frequent switching was assessed via a field evaluation. Preliminary results indicated that magnetic actuator driven switchgear perform commendably on the safety aspect, on-site performance monitoring and online diagnostic test results. However, there are several concerns that need to be addressed such as the ease of installation, substation system requirements, high life cycle cost and reliability of components, before this technology can be used widely.
News Source: Pertanika Journals
ISSN: 0128-7680
Volume: 25
Pages: 61-68
Publisher: Universiti Putra Malaysia Press
Appears in Collections:Journal Content Pages/ Kandungan Halaman Jurnal

Files in This Item:
File Description SizeFormat 
ukmvital_116391+Source01+Source010.PDF475.02 kBAdobe PDFThumbnail
View/Open