Title: The response of a high voltage transformer with various geometries of core joint design
Authors: Omar. SH. Alyozbaky (UPM)
Maryam. M. Isa (UPM)
Mohd Zainal Abidin Ab Kadir (UPM)
Mahdi Izadi (UPM)
Keywords: Core loss
Power transformer
Joints design
Flux distribution
Issue Date: Feb-2017
Description: The core losses in a three phase transformer can be significantly reduced by improving the core joint geometry. The researchers were applied numerous types of T-joint designs in order to reach the optimum design that can be used in three phase transformer to reduction the losses. Two types of T-joint design are presented in this paper; T-joint with 90° butt-lap design and T-joint with 45° mitered design. A 3-phase distribution transformer was simulated in 3D using Ansys Maxwell software. The core loss for a three-leg three phase transformer rated 1000 KVA and the flux density distribution are investigated. The simulation results show the core losses were increased up to 3% and the flux density was increased to reach more than 22% flux density become higher when using T-joint with 90° butt-lap design as compared with T-joint with 45° mitered design.
News Source: Pertanika Journals
ISSN: 0128-7680
Volume: 25
Pages: 21-28
Publisher: Universiti Putra Malaysia Press
Appears in Collections:Journal Content Pages/ Kandungan Halaman Jurnal

Files in This Item:
File Description SizeFormat 
ukmvital_116379+Source01+Source010.PDF968.55 kBAdobe PDFThumbnail
View/Open